PROGRAM Gas Fire Extinguishing Panel, Model : PE-GA2000 is manufactured and tested in accordance to EN 54-2 : 1997 (which is equivalent to MS 1745-2 : 2004) and also conformed to local CIFS requirements.
The discharge can be automatic, using two zones double knock detection system or manual release system by using a 24V DC electrical key switch or mechanical pull bar system applied directly on the gas cylinder. This control and indicators are housed in a compact enclosure finished with signal red epoxy powder paint. This is applicable for all sub-stations, server rooms, transformer rooms, switch rooms and paint boots.
Standard Features
- Power Source Indicators
- Power Failure Indicators
- Zone Fire, Fault and Isolate Indicators
- Bell Isolate Switch and Indicator
- Auxiliary Trip Isolate Switch and Indicator
- Gas Isolate Switch and Indicator
- Fault Buzzer Mute Switch
- Master Reset Switch
- Main on/off Switch
- Test Battery Switch
- Earth Fault Supervisory
- Built-in Delay Discharge Timer (Adjustable)
Power Supply Input | 240V AC 50Hz |
Operating / System | 24V DC |
Charger | Auto / Trickle |
Charging Rate | 300mA (Trickle) 2.5A (Boost) |
End of Line | 8K2 Ohms |
Auxiliary Output | 24V, 1 Amp |
FAP Output | N/O Contact |
Standby Mode | |
Master | 75 mA |
Per Zone (c/w Detectors) | 5 mA |
Flashing Light (Green LED) | 75 mA |
Alarm Mode | |
Master | 140 mA |
Per Trigger Zone | 70 mA |
Output Devices | 200 mA |
Flashing Light (Red LED) | 75 mA |
Per Bell | 30 mA |